Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 242

Appendix
Code table
14−41
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0415
v
(cont.)
Possible digital signals for C0415
^ 7−68
AIF control word (AIF−CTRL)
Permanently assigned bits of AIF−CTRL:
Bit 3: QSP
Bit 7: CINH
Bit 10: TRIP−SET
Bit 11: TRIP−RESET
40
Bit 0
...
...
55
Bit 15
CAN−IN1.W1 or FIF−IN.W1
60
Bit 0
...
...
75
Bit 15
CAN−IN1.W2 or FIF−IN.W2
80
Bit 0
...
...
95
Bit 15
CAN−IN2.W1
100
Bit 0
...
...
115
Bit 15
CAN−IN2.W2
120
Bit 0
...
...
135
Bit 15
Status application I/O
Only active for operation with application
I/O
140
Torque threshold 1 reached (MSET1=MOUT)
141
Torque threshold 2 reached (MSET2=MOUT)
142
Limitation of process controller output reached
(PCTRL1−LIM)
143 ...
172
Reserved
255
Not assigned (FIXED−FREE)
C0416
v
Level inversion of
digital outputs
0
0
Level inversion is switched off
By entering the sum of the selected values
you can invert several outputs
^ 7−73
1
Relay K1
2
X3/A1
4
X3/A2
only application I/O
8
Relay K2
Relay output K2 only with 8200 vector 15 ...
90 kW