Commissioning, V/f characteristic control – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 50

Commissioning
V/f characteristic control
5−9
L
EDB82MV752 EN 5.2
14.
If you want to change other settings, please go to the
ALL
menu
Activate e.g. JOG frequencies
(C0037, C0038, C0039) or
motor temperature monitoring
(C0119)
15.
Go to the
ALL
menu
A Check the fan monitoring setting under code C0608:
– for 8200 motec 0.25...0.37 kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may be
destroyed through overheating!
– for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete:
16.
Select the setpoint
E.g. via potentiometer at
terminals 7, 8, 9
17.
Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH
18.
The drive should now be running.
If the drive does not start, press
u
in
addition