Commissioning
Selection of the correct control mode
5−5
L
EDB82MV752 EN 5.2
Application
Operating mode
Stand−alone drives
C0014
recommended
alternatively
with extremely alternating loads
−4−
−2−
with heavy start conditions
−4−
−2−
with speed control (speed feedback)
−2−
−4−
with high dynamic response (e. g. positioning and infeed drives)
−2−
−
with torque setpoint
−5−
−
with torque limitation (power control)
−2−
−4−
three−phase AC reluctance motors
−2−
−
three−phase sliding rotor motors
−2−
−
three−phase motors with fixed frequency−voltage characteristic
−2−
−
Pump and fan drives with square−law load characteristic
−3−
−2− / −4−
Group drives
(several motors connected to controller)
identical motors and identical loads
−2−
−
different motors and/or changing loads
−2−
−
C0014 = −2−: linear V/f characteristic control
C0014 = −3−: square−law V/f characteristic control
C0014 = −4−: vector control
C0014 = −5−: sensorless torque control