LOaD appLicatiOn/generatOr Output

single pHase load

Always be sure to check the nameplate on the generator

and equipment to insure the wattage, amperage, frequency,

and voltage requirements are satisfactorily supplied by the

generator for operating the equipment.
Generally, the wattage listed on the nameplate of the

equipment is its rated output. Equipment may require

130—150% more wattage than the rating on the nameplate,

as the wattage is influenced by the efficiency, power factor

and starting system of the equipment.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 6 below

when connecting loads.

table 7. Cable selection (60 Hz, single phase operation)

Current

in

amperes

load in Watts

maximum allowable Cable length

at 100

volts

at 200

volts

#10 Wire #12 Wire #14 Wire #16 Wire

2.5

300

600

1000 ft.

600 ft.

375 ft.

250 ft.

5

600

1200

500 ft.

300 ft.

200 ft.

125 ft.

7.5

900

1800

350 ft.

200 ft.

125 ft.

100 ft.

10

1200

2400

250 ft.

150 ft.

100 ft.

15

1800

3600

150 ft.

100 ft.

65 ft.

20

2400

4800

125 ft.

75 ft.

50 ft.

CAUTION: Equipment damage can result from low voltage

NOTICE

If wattage is not given on the equipment’s name plate,

approximate wattage may be determined by multiplying

nameplate voltage by the nameplate amperage.

table 6. power Factor By load

type of load

Power Factor

Single-phase induction motors

0.4-0.75

Electric heaters, incandescent lamps

1.0

Fluorescent lamps, mercury lamps

0.4-0.9

Electronic devices, communication

equipment

1.0

Common power tools

0.8

An inadequate size connecting cable which cannot carry the

required load can cause a voltage drop which can burn out

the appliance or tool and overheat the cable. See Table 7

„

When connecting a resistance load such as an

incandescent lamp or electric heater, a capacity of up

to the generating set’s rated output (kW) can be used.

„

When connecting a fluorescent or mercury lamp, a

capacity of up to the generating set’s rated output (kW)

multiplied by 0.6 can be used.

„

When connecting an electric drill or other power tools,

pay close attention to the required starting current

capacity.

When connecting ordinary power tools, a capacity of up to

the generating set’s rated output (kW) multiplied by 0.8 can

be used.

generator amperage

Table 8 shows the

maximum amps the generator can

provide.

do not exceed the maximum amps as listed.

NOTICE

Motors and motor-driven equipment draw much greater

current for starting than during operation.

danger

Before connecting this generator to any building’s

electrical system, a

licensed electrician must install

an

isolation (transfer) switch. Serious damage to

the building’s electrical system may occur without this

transfer switch.

table 8. generator maximum amps

rated voltage

maximum amps

1Ø 120 Volt

83 X 2 amps (4 wire)

1Ø 240 Volt

83 amps (4 wire)