generatOr shut-DOWn prOceDures

starting (auto mode)

danger

Before connecting this generator to any

building’s electrical system, a

licensed

electrician must install an isolation

(transfer) switch. Serious damage to

the building’s electrical system may occur

without this transfer switch.

NOTICE

When connecting the generator to a isolation (transfer)

switch,

alWaYs have power applied to the generator’s

internal battery charger. This will ensure that the engine

will not fail due to a dead battery

NOTICE

When the MPEC control switch is placed in the

auto

mode, the generator will

automatically start in the

event of commercial power falling below a prescribed

level by means of a contact closure that is generated

automatically by a transfer switch.
In this position (

auto), should an outage occur, the

automatic transfer switch (ATS) will start the generator

automatically via the generator's auto-start contacts

connected to the ATS's start contacts.
Please refer to your ATS installation manual for further

instructions for the correct installation of the auto-start

contacts of the generator to the ATS.

Warning

When running the generator in the

auto mode,

remember the generator can start up at any time without

warning.

never attempt to perform any maintenance

when the generator is in the auto mode.

1. Place the

mpeC Control switch (Figure 37) in the

auto position.

Figure 37. MPEC Control Switch (AUTO)

2. Continue operating the generator as outlined in the

Manual Start-up procedure (start at step 2).

AUTO

MANUAL

OFF/RESET