Troubleshooting (generator) – Multiquip DCA20SPXU2 User Manual

Page 59

Advertising
background image

DCa20SPxu2 SERVPRO

®

• operation and parts manual — rev. #0 (09/23/13) — page 59

trOuBLeshOOting (generatOr)

Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a breakdown,

use the table shown below and on the preeceding pages for diagnosis of the generator and engine. If the problem cannot

be remedied, consult our company’s business office or service center.

troubleshooting (generator )

symptom

possible problem

Solution

Voltage Output

Weak

AC Voltmeter defective?

Check output voltage using a voltmeter.

Is wiring connection loose?

Check wiring and repair.

Is AVR defective?

Replace if necessary.

Defective Rotating Rectifi er?

Check and replace.

Defective Exciter Field?

Check for approximately 17.3 ohms

across J & k on CN1

Low Voltage Output

Is engine speed correct?

Turn engine throttle lever to “High”.

Is wiring connections loose?

Check wiring and repair.

Defective AVR?

Replace if necessary.

High Voltage Output

Is wiring connections loose?

Check wiring and repair.

Defective AVR?

Replace if necessary.

Advertising