Generator start-up procedure (manual) – Multiquip DCA20SPXU2 User Manual

Page 31

Advertising
background image

DCa20SPxu2 SERVPRO

®

• operation and parts manual — rev. #0 (09/23/13) — page 31

generatOr start-up prOceDure (ManuaL)

BeFore starting

1. Place the

main, g.F.C.i., and aux. circuit breakers

(Figure 24) in the

OFF position prior to starting the

engine.

Figure 24. Main, Aux. and GFCI

Circuit Breakers (OFF)

2. Connect the load to the

receptacles or the output

terminal lugs as shown in Figure 12. These load

connection points can be found on the output terminal

panel and the output terminal panel’s hard wire hookup

panel.

3. Tighten terminal nuts securely to prevent load wires

from slipping out.

4. Close all engine enclosure doors (Figure 25).

Figure 25. Engine Enclosure Doors

Caution

The engine’s exhaust contains harmful emissions.

alWaYs have adequate ventilation when operating.

Direct exhaust away from nearby personnel.

Warning

never manually start the engine with the main, gFCi

or auxiliary circuit breakers in the on (closed) position.

INCORRECT

CORRECT

starting (manual)

1. Place the

mpeC control switch in the manual

position to start the engine (Figure 26) position.

Figure 26. MPEC Control Switch

(Manual Position)

2. Verify that the

engine running status LED on the

MPEC module (Figure 27) is lit (ON) after the engine

has started

Figure 27. Engine Running (LED ON)

3. The generator’s frequency meter (Figure 28) should

be displaying the 60 cycle output frequency in

Hertz.

Figure 28. Frequency Meter

4. The generator’s AC-voltmeter (Figure 29) will display

the generator’s output in

volts.

Figure 29. Voltmeter

AUTO

MANUAL

OFF/RESET

AUTO

MANUAL

OFF/RESET

LOW OIL PRESSURE

HIGH COOLANT TEMPERATURE

OVERCRANK
OVERSPEED
ENGINE RUNNING

MOOOOO-20001Q

Hz

V

Advertising