• operation and parts manual — rev. #0 (09/23/13) — page 29

Day-to-day addition of coolant is done from the recovery

tank. When adding coolant to the radiator,

do not remove

the radiator cap until the unit has completely cooled. See

Table 10 for engine, radiator, and recovery tank coolant

capacities. Make sure the coolant level in the recovery tank

is always between the “H” and the “L” markings.

operation in Freezing Weather

When operating in freezing weather, be certain the proper

amount of antifreeze (Table 11) has been added.

Cleaning tHe radiator

The engine may overheat if the radiator fins become

overloaded with dust or debris. Periodically clean the

radiator fins with compressed air. Cleaning inside the

machine is dangerous, so clean only with the engine turned

off and the

negative battery terminal disconnected.

air Cleaner

Periodic cleaning/replacement is necessary. Inspect it in

accordance with the

isuzu engine owner’s manual.

Fan Belt tension

A slack fan belt may contribute to overheating, or to

insufficient charging of the battery. Inspect the fan belt for

table 10. Coolant Capacity

Engine and Radiator

1.74 gal (606 liters)

Reserve Tank

0.26 gal. (1 liter)

table 11. anti-Freeze operating temperatures

Vol %

Anti-

Freeze

Freezing Point

Boiling Point

°C

°F

°C

°F

50

-37

-34

108

226

NOTICE

When the antifreeze is mixed with water, the antifreeze

mixing ratio

must be less than 50%.

damage and wear and adjust it in accordance with the

isuzu engine owner’s manual.
The fan belt tension is proper if the fan belt bends 10 to 15

mm (Figure 22) when depressed with the thumb as shown

below.

Figure 22. Fan Belt Tension

BatterY

This unit is of negative ground

do not connect in reverse.

Always maintain battery fluid level between the specified

marks. Battery life will be shortened, if the fluid level are

not properly maintained. Add only distilled water when

replenishment is necessary.
do not over fill. Check to see whether the battery

cables are loose. Poor contact may result in poor starting

or malfunctions.

always keep the terminals firmly

tightened. Coating the terminals with an approved battery

terminal treatment compound. Replace battery with only

recommended type battery.
The battery is sufficiently charged if the specific gravity

of the battery fluid is 1.28 (at 68° F). If the specific gravity

should fall to 1.245 or lower, it indicates that the battery is

dead and needs to be recharged or replaced.
Before charging the battery with an external electric source,

be sure to disconnect the battery cables.

Caution

NEVER place hands near the belts or fan

while the generator set is running.