Generator shut-down procedures – Multiquip DCA20SPXU2 User Manual
Page 34
page 34 — dCa20spxu2 servpro
®
• operation and parts manual — rev. #0 (09/23/13)
normal sHutdoWn proCedure
To shutdown the generator, use the following procedure:
1. Place the
main, g.F.C.i., and aux. circuit breakers
(Figure 38) in the
OFF position.
Figure 38. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
Warning
never stop the engine suddenly except in an
emergency.
generatOr shut-DOWn prOceDures
3. Place the
mpeC Control switch (Figure 39) to the
oFF/reset position.
Figure 39. MPEC Control Switch (Off/Reset)
4. Verify that
all the status LEDs on the MPEC display
are
OFF (not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.
emergenCY sHutdoWn proCedure
1. Place the
main, g.F.C.i., and aux. circuit breakers
(Figure 38) in the
OFF position.
AUTO
MANUAL
OFF/RESET