‎Chapter 3 BFM136 Display Operations

Menu Operations

32

BFM136 Branch Feeder Monitor

Label

Parameter

Options

Default

Description

Ratio V1-V3

V1-V3 voltage
transformer
ratio correction

factor

0.700 to 1.300

1.000

The ratio of the true
transformer ratio to the
marked ratio.

Angle V1-V3

V1-V3
transformer

phase angle
error, minutes

-600 to 600

0

The phase
displacement, in

minutes, between the
primary and secondary

values. The phase
angle of a voltage

transformer is positive
when the secondary

value leads the primary

value.

Ratio I1-I36

I1-I36 current
transformer
ratio correction

factor

0.700 to 1.300

1.000

The ratio of the true
transformer ratio to the
marked ratio.

Angle I1-I36

I1-I36
transformer

phase angle
error, minutes

-600 to 600

0

The phase
displacement, in

minutes, between the
primary and secondary

values. The phase
angle of a current

transformer is positive
when the secondary

value leads the primary
value.

Device Options

This menu allows you to select some user-configurable device options or put
the BFM136 into energy test mode.

To enter the menu, select the Options entry from the main menu, then press
ENTER. For instructions on navigating in the menu, see

Viewing and

Changing Setup Items

.

The following table lists available options.

Label

Parameter

Options

Default

Description

PowMode

Power
calculation

mode

Reactive,
NonActive (non-

active power)

Reactive

The method used for
calculating reactive

and apparent powers

ErgyRoll

Energy roll
value

100000.0-
100000000.0
kWh

100000000.0 The value at which

energy counters roll

over to zero

TestMode

Energy test
mode

OFF, Wh, varh OFF

Setting this option
puts the device into

the energy test mode

PlsConst

Wh LED pulse
rate,

Wh/pulse

0.01-100.00

5.40Wh/pulse
(one

equivalent
disk

revolution)

LED pulse constant -
the amount of

accumulated energy
giving one pulse via

“Wh” LED

WhLEDSrc Energy LED

source

1-40, None

1

Selects a submeter as
a LED pulsing source

Communication Ports

These two menus allow you to configure parameters for communication
ports COM1 and COM2. The BFM136 automatically detects a replaceable
communication module and will not allow you to change the baud rate and

data format for the Dial-up modem, and for the Ethernet and RF modules.

Options

Exit

Options PowMode

Reactive