‎Chapter 4 PAS Application Software

Configuring Billing Energy and TOU Registers

48

BFM136 Branch Feeder Monitor

The following table describes the setpoint options.

Option

Range

Description

Trigger
parameter

See Appendix D The trigger parameter that is used as an argument in

the logical expression

Operate limit

The threshold (in primary units) at which the
conditional expression would be evaluated to true. Not

applicable for time triggers.

Release limit

The threshold (in primary units) at which the
conditional expression would be evaluated to false.

Defines the hysteresis for analog triggers. Not
applicable for digital triggers.

Operate delay 0.1-999.9 sec

The time delay before operation when the operate
conditions are fulfilled

Release delay 0.1-999.9 sec

The time delay before release when the release

conditions are fulfilled

Action

See Appendix D The action performed when the setpoint expression is

evaluated to true (the setpoint is in operated state)

Using Numeric Triggers

For numeric (analog) triggers, a setpoint allows you to specify two thresholds
for each trigger to provide hysteresis (dead band) for setpoint operations.
The operate limit defines the operating threshold, and the second release
limit defines the release threshold for the trigger. If you do not want to use
hysteresis for the trigger, set the release limit to the same as the operate
limit.

Using Time Triggers

If you want the setpoint actions to be synchronized with the clock, for
example, to provide recording interval data, use the minute time interval
trigger that generates periodic events synchronized with the device clock.

Delaying Setpoint Operations

Two optional delays can be added to each setpoint to extend monitoring a
setpoint trigger for a longer time before making a decision on whether the
expected event occurred or not. When a delay is specified, the logical
controller will change the setpoint status only if all conditions are asserted for
a period at least as long as the delay time.

Using Setpoint Events

When a setpoint status changes, i.e., a setpoint event is either asserted or
de-asserted, the following happens in your device:

1. The new setpoint status is logged to the setpoint status register that can

be monitored via communications from the user application software in
order to give a real-time indication on the expected event.

2. The operated setpoint status is latched to the setpoint alarm register

accessible through communications. The register holds the last setpoint
alarm status until it is explicitly cleared via communications.

Recording Setpoint Events

Time-tagged setpoint events can be recorded to the submeter event log if
you select it as the setpoint action. The Event recorder logs any setpoint
transition event: both when the setpoint is operated, and when it is released.

Configuring Billing Energy and TOU Registers

The BFM136 provides four total/summary energy and six parallel tariff
energy and maximum demand registers for each individual submeter. The
registers can be linked to any internal energy source or to another submeter.