‎Chapter 4 PAS Application Software

Configuring Billing Energy and TOU Registers

50

BFM136 Branch Feeder Monitor

Parameter

Options

Default

Description

Billing/TOU Registers

Units

kWh, kvarh, kVAh None

The register measurement units. It is set
automatically.

Register Source List

Source
Input

None

kWh IMPORT
kWh EXPORT

kvarh IMPORT
kvarh EXPORT

kVAh TOTAL
Submeter 1 -
Submeter 40

1

None

Links an energy source to the target
register of all metering submeters, or links

all registers of a source submeter to a
totalization submeter.

Multiplier

0.001 to 100.000 0.100

The multiplication factor for the energy

source.

Target

Reg#1- Reg#3
Submeter 1 -
Submeter 40

1

None

Defines the target register for the energy
source. It is set automatically for target
energy registers.

1

Linking a submeter to another totalization submeter connects all its

configured energy registers to the corresponding registers of the target
submeter.

Totalization Submeters

If you wish to automatically totalize energy measured by a number of
submeters by using a separate totalization submeter, select a source
submeter in the Source Input column on the Register Source List pane

(starting with source 5), and then select the desired target totalization
submeter in the Target column. Repeat these steps for all source submeters
while selecting the same totalization submeter as the target.

Selecting a submeter as a target automatically connects all active energy
registers of the source submeters to its energy registers, thus making it a
totalization submeter. Note that each totalization submeter takes its own
communication address in a sequential order along with the metering
submeters (see

Submeter Addressing

).

Configuring the Daily Tariff Schedule

To configure your daily tariff schedule, select Energy/TOU from the Meter
Setup menu, and then click on the TOU Daily Profiles tab.

The daily profile setup allows you to specify the daily tariff change points with
a 15-minute resolution for six tariffs and four seasons.