‎Chapter 4 PAS Application Software

General Meter Setup

BFM136 Branch Feeder Monitor

43

General Meter Setup

This section describes how to configure the BFM136 for your particular
environment and application using PAS.

Basic Meter Setup

Before operating your meter, provide the device with basic information about
your electrical network.

To enter the setup dialog, select the device site from the list box on the PAS
toolbar, and then select General Setup from the Meter Setup menu.

The following table lists available device configuration options.

Parameter

Options

Default

Description

Basic Configuration

PT Ratio

1.0-6500.0

1.0

The phase potential transformer’s
primary to secondary ratio

Primary current

1-10000 A

50A

The HACS primary current of the
submeter’s; for information only.

Nominal frequency 50, 60 Hz

60Hz

The nominal power frequency

Demand Setup

Block power
demand period

1, 2, 5, 10, 15, 20,
30, 60 min

30

The length of the demand period for
power demand calculations

The number of
blocks in the sliding

window

1-15

1

The number of block demand periods
to be averaged for sliding window

demands

Volt demand period 0-9000 sec

900 sec

The length of the demand period for
volt demand calculations

Ampere demand
period

0-9000 sec

900 sec

The length of the demand period for
ampere demand calculations

Device Options

Power calculation
mode

S=f(P, Q) (using
reactive power),
Q=f(S, P) (using

non-active power)

S=f(P, Q)

The method used for calculating
reactive and apparent powers (see

“Power Calculation Modes” below)