‎Chapter 3 BFM136 Display Operations

Menu Operations

34

BFM136 Branch Feeder Monitor

Label

Parameter

Options

Default

Description

Country

Country code

Default, or
country name

Default

Defines a currency and
calendar settings. The default
setting stands for the U.S.A.

Daylight

Daylight saving

time (DST)
option

Disabled,

Enabled

Disabled

When DST is disabled, the

RTC will operate in standard
time only. When enabled, the

BFM136 will automatically
update the time at 2:00 AM at

the pre-defined DST switch
dates.

DST Mon DST start month January-

December

April

The date when Daylight

Saving Time begins. The DST
switch point is specified by the

month, week of the month and
weekday. By default, DST

starts at 2:00 AM on the first
Sunday in April of each year.

DST
Week

DST start week
of the month

First, Second,
Third, Fourth,
Last

First

DST Day DST start day of

the week

Sunday-

Saturday

Sunday

End Mon DST end month January-

December

October

The date when Daylight
Saving Time ends. The DST
switch point is specified by the

month, week of the month and

weekday. By default, DST
ends at 2:00 AM on the last

Sunday in October of each
year.

End Week DST end week

of the month

First, Second,
Third, Fourth,

Last

Last

End Day

DST end day of
the week

Sunday-
Saturday

Sunday

Meter Security

This menu allows you to change the user password and define a level of the
device security for accessing the BFM136 through communication ports.

To enter the menu, select the Access entry from the main menu, and then
press the ENTER button. For instructions on navigating in the menu, see

Viewing and Changing Setup Items

.

The following table lists available options.

Label

Parameter

Options

Default

Description

Password

User
password

0-99999999

Factory set
(consult
your dealer)

A user password for
accessing the device menus.
It is effective for the display

and for all ports

Com.Pass

Remote
password

checking

OFF, ON

ON

Controls password checking
when the BFM136 is

accessed through
communication ports

Display Settings

This menu allows you to configure options for the BFM136 display.

To enter the menu, select the Display entry from the main menu, and then
press the ENTER button.

For instructions on navigating in the menu, see

Viewing and Changing Setup

Items

.

The following table lists available options.

Label

Parameter

Options

Default

Description

Update

Display update
rate

1-10 sec

1 sec

Defines the interval between
display updates

Scroll

Auto scroll
interval

None, 2-15
sec

None

Defines the scroll interval for
the main data display or

disables auto scroll

Auto Ret

Auto return to
the main screen

Disabled,
Enabled

Enabled

Enables automatic return to
the main display if no buttons

are pressed for 5 minutes

Access Exit

Access Password
9

ENTER

Display Exit

Display Update

1

ENTER

Advertising