‎Appendix A Technical Specifications

60

BFM136 Branch Feeder Monitor

Appendix A

Technical Specifications

Environmental Conditions

Indoor use only

BFM is intended for operation in environment where normally only non-
conductive pollution occurs as defined for pollution degree 2 (UL61010,
3.6.6.2)

Operating Temperature: -40°C to 70°C (-40°F to 158°F)
Storage Temperature: -40°C to 80°C (-40°F to 176°F)
Humidity: 0 to 95% non-condensing
Altitude: 2,000m max

Input Ratings

Parameter

Value

Fundamental frequency

50/60 Hz

AC Voltage

4 wires, 3 phases+ neutral

Reference Voltage

(115) 88-136 VAC or
(230/400 – 277/480) 176-320 VAC

Maximum Line to Neutral voltage

320 V

Maximum Line to Line voltage

544V

Burden per phase

<1.5W

AC Voltage for Measurement and

Power supply

Maximal apparent power consumed

from power line < 10VA

Isolation

2.5 kV RMS, 60Hz, 1 min
Leakage current < 0.005A per circuit
Impulse 1.2/50μS 6 kV

Fuse rating

6A, 600V

AC Current

36 current circuits

Maximum measurable current Imax

(In=50A)

400 A

Test current

15 A

Maximum overcurrent for 0.5 cycle of

fundamental frequency

3000 A

Burden per phase

< 1 VA

Isolation

4 kV RMS, 60Hz, 1 min

LCD Display

No. Of Digits

2 Rows, 16 digits in each

Operating Temperature:

-20°C to 70°C (-4°F to 158°F)

Non-volatile Memory storage life

20 years

RTC storage upon loss of power

24 Hours minimum

1 Week typical

Push buttons

4

Voltage inputs terminal

10 AWG Max.

Communication Ports

COM2 (Optional modules)

Serial EIA RS-232 optically isolated port

Connector Type: DB9 female.
Baud Rate: up to 115.2 kbps.
Supported Protocols: Modbus RTU/ASCII.

RS-422/RS-485 optically isolated port

Connector Type: removable, captured-wire, 5 terminals.
Wire Size: up to 12 AWG (up to 2.5 mm

2

).

Baud Rate: up to 115.2 kbps.