Publication 193-QR003B-EN-P - October 2009

Grounding

The following grounding recommendations are provided to ensure electromagnetic
compatibility compliance during installation:

•

The earth ground terminal of the E3 Overload Relay shall be connected to a solid
earth ground via a low-impedance connection

•

Installations employing an external ground fault sensor shall ground the cable shield
at the sensor with no connection made at the E3 Plus Overload Relay

•

The PTC thermistor cable shield shall be grounded at the E3 Plus Overload Relay
with no connection made at the opposite end

Wiring Diagrams

Figure 5: Three-Phase D.O.L & Single-Phase Wiring Diagrams

ATTENTION

!

When working on energized circuits, do not rely on the voltage and
current information provided by the E3 and E3 Plus for personal
safety. Always use a portable voltage or current measurement device
and measure the signal locally.

E3/E3Plus

L 1

L 2

L 3

2 /T 1

4 /T 2

6 /T 3

E3/E3Plus

L 1

L 2

L 3

2 /T 1

4 /T 2

6 /T 3

L 1

2 /T 1

4 /T 2

6 /T 3

2 /T 1

4 /T 2

6 /T 3

2/T1

4/T2

6/T3

M

T1

E3/E3Plus

L 1

2/T1

4/T2

6/T3

M

T1

T2

T3

S.C.P.D.

Three-Phase Direct-On-Line

Wiring Diagram

Single-Phase Full-Voltage

Wiring Diagram

T2

L 2

L 3

L 2

E3/E3Plus

L 1

L 2

L 3

Voltage Input Module

(For 193/592-EC5 only)

L 1

L 2

Voltage Input Module

(For 193/592-EC5 only)