Figure 13: Node Address Switches

Note: For node address switch values in the range of 0…63, cycle power to the E3 Overload Relay to
initialize the new setting.

Setup Requirements

Setup for Cat. Nos. 193/592-EC1/EC2/EC3/EC5 Overload Relays

After the E3 Overload Relay is installed according to the guidelines specified in this manual,
apply power to the overload relay’s DeviceNet connector. After applying power, the following
sequence should occur:

1. The Trip relay should close 2.35 seconds later and the TRIP/WARN LED will not

flash (unless a Non-Volatile Fault previously existed or a fault condition is present).

2. At the same time, the NETWORK STATUS LED should flash green for

approximately two seconds, then red for a 1/4 second. If autobaud is enabled and the
E3 Overload Relay is connected to an active network, the green LED will continue to
flash once the baud rate has been determined. If the E3 Overload Relay is not
connected to an active network, the LED will not continue to flash.

3. Once the E3 Overload Relay has been allocated by a master, the NETWORK

STATUS LED will turn solid green.

After being powered up, use the DeviceNet Configuration Terminal (Cat. No. 193-DNCT) in
order to set up the parameters. There are five basic parameters that need to be established
before using the protective functions. These parameters are listed under the OVERLOAD
SETUP menu and include: Single/Three Phase, Full Load Current (FLA) Setting, Trip Class,
Overload/PTC Reset mode, and Overload Reset Level. (Note: You will need to program
additional parameters when customer-supplied CTs are used.)
Once these parameters are set, the E3 Overload Relay is functional. Use the ADVANCED
SETUP menu to set other parameters per the specific application requirements.

Table 2: Node Address Setting

Switch Settings

Description

0…63

The node address setting is determined by the switch values when set in this range.

64…99

For switch settings in this range, the node address setting is determined by the software
setting using the RSNetWorx for DeviceNet configuration tool.

99

Factory default setting.