Rockwell Automation 193/592-EC1/EC3/EC5 E3 and E3 Plus Solid-State Overload Relay - Quick Reference User Manual

Page 20

Advertising
background image

20

Publication 193-QR003B-EN-P - October 2009

➊ The inhibit time setting parameters are applicable to both the trip and warning functions.
➋ FLA Setting range and default values are dependent upon the current rating of the product. See the user

manual for more information.

Phase loss trip level is factory-set at a current imbalance greater than or equal to 100% and is not

user-adjustable.

➍ Must use Ground Fault Sensors (Cat. No. 193-CBCT_).

Stall protection is only applicable during the motor starting sequence. If any phase of current falls below the

programmed Stall Trip Level, stall protection is disabled.

➏ 50…100% for devices with FRN 1.003 and earlier.
➐ Available on 193/592-EC5 only.

Under
Consumed
kVAR ➐

Disabled

0…32767

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Consumed
kVAR ➐

Disabled

0…32767

0.1…25.0 s

1.0 s

0…250 s

10 s

Under
Generated
kVAR ➐

Disabled

-32767…0

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Generated
kVAR ➐

Disabled

-32767…0

0.1…25.0 s

1.0 s

0…250 s

10 s

Under Power
kVA ➐

Disabled

0…32767

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Power kVA

Disabled

0…32767

0.1…25.0 s

1.0 s

0…250 s

10 s

Under Power
Factor Lagging

Disabled

-100…0

-90

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Power
Factor Lagging

Disabled

-100…0

-95

0.1…25.0 s

1.0 s

0…250 s

10 s

Under Power
Factor Leading

Disabled

0...100

90

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Power
Factor Leading

Disabled

0...100

95

0.1…25.0 s

1.0 s

0…250 s

10 s

Table 3: Trip Summary

Trip

Function

Trip

Enable

Factory
Default

Trip Level Settings

Trip Delay Settings

Inhibit Time

Settings

Range Default

Range

Default

Range

Default