Rockwell Automation 193/592-EC1/EC3/EC5 E3 and E3 Plus Solid-State Overload Relay - Quick Reference User Manual
Page 25

25
Publication 193-QR003B-EN-P - October 2009
Protective Trip/Warning Summaries & Parameter Group Listing
(Cat. No. 193-EC4)
Table 7: Trip Summary
Trip
Function
Trip Enable
Factory
Default
Trip Level Settings
Trip Delay Settings
Inhibit Time
Settings
Range
Default
Range
Default
Range
Default
Ground Fault
Disabled
0.02…5 A
2.5 A
0.0…25 s
0.5 s
0…250 s
10 s
L1
Undercurrent
Disabled
0.2…45 A
—
0.1…25 s
1.0 s
0…250 s
1.0 s
L2
Undercurrent
Disabled
0.2…45 A
—
0.1…25 s
1.0 s
0…250 s
1.0 s
L3
Undercurrent
Disabled
0.2…45 A
—
0.1…25 s
1.0 s
0…250 s
1.0 s
L1
Overcurrent
Disabled
0.4…270 A
—
0.1…25 s
1.0 s
0…250 s
1.0 s
L2
Overcurrent
Disabled
0.4…270 A
—
0.1…25 s
1.0 s
0…250 s
1.0 s
L3
Overcurrent
Disabled
0.4…270 A
—
0.1…25 s
1.0 s
0…250 s
1.0 s
L1 Loss
Disabled
—
—
0.5…25 s
0.5 s
0…250 s
1.0 s
L2 Loss
Disabled
—
—
0.5…25 s
0.5 s
0…250 s
1.0 s
L3 Loss
Disabled
—
—
0.5…25 s
0.5 s
0…250 s
1.0 s
Comm Fault
Disabled
—
—
—
—
—
—
Comm Idle
Disabled
—
—
—
—
—
—
Remote Trip