Table 15: IEC Type 1 and Type II Fuse Coordination with Bulletin 100-C and 100-D
Contactors per EN60947-4-1
Cat. No.
Contactor Max.
Starter
FLC [A]
Prospective
Short-Circuit
Current I
r
[A]
Conditional
Short-Circuit
Current I
q
[A]
Max.
Voltage
[V]
Type I
with Class
J Fuse [A]
Type II
with
Class J
Fuse [A]
193-EC1
193-EC2
193-EC3
193-EC4
193-EC5
_B
100-C09
9
1000
100000
600
20
15
100-C12
12
20
20
100-C16
16
30
30
100-C23
23
40
40
_D
100-C30
30
3000
50
50
100-C37
37
50
50
100-C43
43
70
70
_E
100-C60
60
80
80
100-C72
72
100
100
100-C85
85
5000
150
150
FF, ZZ
100-D95
95
10000
200
200
FF, ZZ
100-D110
110
200
200
FF, ZZ
100-D140
140
250
250
GF, ZZ
100-D180
180
300
300
GG, ZZ
100-D210
210
400
400
100-D250
250
400
400
100-D300
300
500
500
HG, ZZ
100-D210
210
400
400
100-D250
250
400
400
100-D300
300
500
500
JG, ZZ
100-D300
300
500
500
100-D420
420
600
600