Protective Trip/Warning Summaries & Parameter Group Listing
(Cat. Nos. 193/592-EC1/EC2/EC3/EC5)

Table 3: Trip Summary

Trip

Function

Trip

Enable

Factory
Default

Trip Level Settings

Trip Delay Settings

Inhibit Time

Settings

Range Default

Range

Default

Range

Default

Overload

Enabled

Trip Class

5…30

Trip Class

10

Phase Loss

Enabled

0.1…25.0 s

1.0 s

0…250 s

0 s

Ground Fault
(193/592-EC2)

Disabled

Internal 1…5 A

2.5 A

0.0…25.0 s

0.5 s

0…250 s

10 s

Ground Fault
(193/592-EC3)

Disabled

External

0.02…5 A ➍

2.5 A

0.0…25.0 s

0.5 s

0…250 s

10 s

Stall

Disabled

100…600% ➎

600% ➎

0…250 s

10 s➎

Jam

Disabled

50…600%

250%

0.1…25.0 s

5.0 s

0…250 s

10 s

Underload

Disabled

10…100% FLA

50%

0.1…25.0 s

5.0 s

0…250 s

10 s

PTC

Disabled

Current
Imbalance

Disabled

10…100%

35%

0.1…25.0 s

5.0 s

0…250 s

10 s

Comm Fault

Enabled

Comm Idle

Disabled

Remote Trip

Disabled

Voltage Input
Module
Hardware Fault

Disabled —

Undervoltage
L-L ➐

Disabled

0...65535

100

0.1…25.0 s

1.0 s

0…250 s

10 s

Overvoltage L-L

Disabled

0...65535

500

0.1…25.0 s

1.0 s

0…250 s

10 s

Voltage
Unbalance ➐

Disabled

0…100

75

0.1…25.0 s

1.0 s

0…250 s

10 s

Phase Rotation

Disabled 1…2

1

0…250 s 10 s

Under
Frequency ➐

Disabled

0…250

57

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Frequency

Disabled

0…250

63

0.1…25.0 s

1.0 s

0…250 s

10 s

Under Real
Power ➐

Disabled

0…32767

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Real
Power ➐

Disabled

0…32767

0.1…25.0 s

1.0 s

0…250 s

10 s