Protective Trip/Warning Summaries & Parameter Group Listing
(Cat. Nos. 193/592-EC1/EC2/EC3/EC5)

Table 3: Trip Summary

Trip

Function

Trip

Enable

Factory
Default

Trip Level Settings

Trip Delay Settings

Inhibit Time

Settings ➊

Range Default

Range

Default

Range

Default

Overload

Enabled

➋

➋

Trip Class

5…30

Trip Class

10

—

—

Phase Loss

Enabled

➌

➌

0.1…25.0 s

1.0 s

0…250 s

0 s

Ground Fault
(193/592-EC2)

Disabled

Internal 1…5 A

2.5 A

0.0…25.0 s

0.5 s

0…250 s

10 s

Ground Fault
(193/592-EC3)

Disabled

External

0.02…5 A ➍

2.5 A

0.0…25.0 s

0.5 s

0…250 s

10 s

Stall

Disabled

100…600% ➎

600% ➎

0…250 s

➎

10 s➎

—

—

Jam

Disabled

50…600%

250%

0.1…25.0 s

5.0 s

0…250 s

10 s

Underload

Disabled

10…100% FLA

➏

50%

0.1…25.0 s

5.0 s

0…250 s

10 s

PTC

Disabled

—

—

—

—

—

—

Current
Imbalance

Disabled

10…100%

35%

0.1…25.0 s

5.0 s

0…250 s

10 s

Comm Fault

Enabled

—

—

—

—

—

—

Comm Idle

Disabled

—

—

—

—

—

—

Remote Trip

Disabled

—

—

—

—

—

—

Voltage Input
Module
Hardware Fault

➐

Disabled —

—

—

—

—

—

Undervoltage
L-L ➐

Disabled

0...65535

100

0.1…25.0 s

1.0 s

0…250 s

10 s

Overvoltage L-L

➐

Disabled

0...65535

500

0.1…25.0 s

1.0 s

0…250 s

10 s

Voltage
Unbalance ➐

Disabled

0…100

75

0.1…25.0 s

1.0 s

0…250 s

10 s

Phase Rotation

➐

Disabled 1…2

1

—

—

0…250 s 10 s

Under
Frequency ➐

Disabled

0…250

57

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Frequency

➐

Disabled

0…250

63

0.1…25.0 s

1.0 s

0…250 s

10 s

Under Real
Power ➐

Disabled

0…32767

0.1…25.0 s

1.0 s

0…250 s

10 s

Over Real
Power ➐

Disabled

0…32767

0.1…25.0 s

1.0 s

0…250 s

10 s