839E Solid-State Flow Sensors User Manual

8

Pub #10000004735 Ver 03, May 2012

Wiring

• The sensor tip should be completely

surrounded by medium.

• Position the sensor tip in the area of

maximum fluid velocity (pipe center).

• Minimum sensor immersion length:

L1 ±10 mm.

Figure 4 Installation conditions

Orientation:

• For horizontal pipes: lateral installation.

Note!
Installation from above (see Figure 4) only if
the pipe is completely filled with medium
during operation.

• For vertical pipes: installation in the

ascending pipeline.

• Installation of 839E by min. 3° inclination,

because of self draining.

Figure 5 Correct orientation

• Do not install in down

pipes open towards the
end.

• The sensor tip should

never touch the pipe
wall.

Figure 6 Incorrect installation