Rockwell Automation 839E Solid-State Flow Sensors User Manual

Page 27

Advertising
background image

839E Solid-State Flow Sensors User Manual

Pub #10000004735 Ver 03, May 2012

25

Operating conditions

• Any orientation
• Top housing section can be rotated 310°

Operating conditions: Environment

• Ambient temperature range

–40…+85 °C (–40…185 °F)

• Storage temperature

–40…+85 °C (–40…185 °F)

• Climate class

4K4H as per DIN EN 60721-3-4

• Degree of protection

IP65 complete housing

• Shock resistance

50 g as per DIN IEC 68-2-27 (11 ms)

• Vibration resistance

20 g as per DIN IEC 68-2-6 (10-2000Hz)
4 g as per guidelines of German Lloyd GL

• Electromagnetic compatibility

Interference emission as per IEC 61326, class B equipment
Interference immunity as per IEC 61326, Appendix A (industry) and
NAMUR Recommendation NE21; EMC influence: d 0.5%

Operating conditions: Process

• Process flow limits

Liquids: 0.03…3.0 m/s (0.1…9.84 ft/s)

• Process temperature limits

–20…85 °C (–4…185 °F)

Note!

The sensor can be exposed up to 130°C (266°F) without damage. Monitoring switches shut
off automatically at T ≥ 85°C (185F) and starts again at T ≤ 85°C (185°F).

• Process pressure limits

p/T load diagram as per DIN 43763 or Dittrich/Kohler (or as per ASME/ANSI PTC 19.3)

Advertising