Rockwell Automation 839E Solid-State Flow Sensors User Manual

Page 14

Advertising
background image

839E Solid-State Flow Sensors User Manual

12

Pub #10000004735 Ver 03, May 2012

Navigating the “Learn” function

Figure 10 Navigating the “Learn” function using the Calibration (CAL) function group as an
example

Select the HIF (Learn High Flow) or LOWF (Learn Low Flow) function with the E key

Select the “RUN” function with the + key, learn function is initialized

Select the “WAIT” function with the + key, press for longer than 2 sec.

Accept (“learn”) the current measured value after approx. 10 sec. - “OK” appears on the

display

If “NOK” (not OK) appears on the display after 60 sec., no current measured value was set

Return to the CAL function group (Home position) with the E key

Notes!

1. Programming buttons [E], [-], and [+] may need to be pressed and held for several

seconds before displaying the expected response.

2. When performing a calibration the 839E may require up to 60 seconds to learn the high

or low flow rate. The display will indicate “WAIT” during the learn process.

3. After configuring the 839E to the desired settings, press and hold the [E] key until

“SAVE” appears; press the [+] or [-] key until “YES” appears. Press and hold the [E] key
until “SAVE” appears. Depending on the configuration changes the display may
indicate a number or a blinking “INIT.” Wait for the blinking “INIT” to change to another
value. This indicates the 839E is ready for operation.