Rockwell Automation 839E Solid-State Flow Sensors User Manual

Page 17

Advertising
background image

839E Solid-State Flow Sensors User Manual

Pub #10000004735 Ver 03, May 2012

15

Basic settings

Function

group

Function

(display)

Description

BASE
(basic
functions)

Display assignment:
OFF
Display of current measured value or of configured
switch point (switch 1)
Display of current measured value or of configured
switch point (switch 1) rotated 180°
Display of current medium temperature
Display of current medium temperature rotated 180°
Factory setting: current measured valued in %

Display medium temperature unit °C or °F
Factory setting: °C
NOTE: Only visible if the current medium
temperature is selected in the DISP mode.

Measured value damping with regard to display
value and output:
0 (no damping) or 9…40 sec. (in increments of 1
second)
Factory setting: 0 sec.

Behavior as per DESINA: The PIN of the M12
connector is assigned in accordance with the
guidelines of DESINA.
(DESINA = DistributEd and Standardized INstAllation
technology for machine tools and manufacturing
systems)

CAL
(Calibration)

Setting for maximum flow rate occurring.
100% value

Setting for minimum flow rate occurring.
0% value

Advertising