DIP-Switch Selection Settings—Transmitter

DIP-Switch Selection Settings—Receiver

After mounting, electrically connecting and aligning the GuardShield
safety light curtain, it is now possible to configure your system.

To begin system configuration, use the security tool provided to
loosen the screw in the configuration door.

Note:

The configuration door screw is a captive screw.

Note:

The transmitter can only be configured for beam coding
and Machine Test Signal. If neither of these
configurations are required, then it is only necessary to
configure the GuardShield receiver.

Identify and set the appropriate DIP-switches for the configuration
desired.

DIP-switch identification and function is explained in the tables below.

Follow the Teach Function Procedure to reconfigure the GuardShield.

When delivered from the factory, the following settings are
configured.

Receiver—Factory Settings

Transmitter—Factory Settings

Settings for Mode of Operation—Receiver

Door Status

Switch

Teach

Button

Door Status

Switch

Teach

Button

IMPORTANT

After each reconfiguration of the GuardShield,
test the system for proper configuration and
operation before placing the guarded machine
in operation.

Switch

Switch Function

Default
Setting

Description

1

Mode Activation—Combination
activates
one of the following modes:
Guard only, Start interlock, Restart
Interlock

ON

Guard Only

2

ON

3

MPCE Monitoring disable

ON

Disabled

4

Fixed Blanking Activate

OFF

Disabled

5

Floating Blanking Activate—Single
Beam

OFF

Switches 5&6 cannot be activated
“On” at the same time.

6

Floating Blanking Activate—Two
Beams

OFF

7

Set Beam Coding

OFF

Disabled

8

Not used

OFF

Switch

Switch Function

Default
Setting

Description

1

Set Beam Coding

OFF

Disabled

2

Machine Test Signal

OFF

OFF: Signal High active—No connection or
connect normally open
ON: Signal Low active—Connect N/C

Switch 1

Switch 2

Condition

Operation

ON

ON

Guard Only

ON/OFF
Operation

OFF

ON

Start Interlock
(Push Button
Reset)

Interlock at start up—Reset by actuation of
pushbutton switch

OFF

OFF

Restart
Interlock

Interlock at interruption of sensing area—Reset by
actuation of pushbutton switch

ON

OFF

Start
Interlock

Interlock at start up—Reset by Interruption/
restoration of sensing area for <1 sec

ATTENTION

Every modification at the DIP switches must be
stored in the memory of the device through the
Teach function.

IMPORTANT

GuardShield light curtains with ArmorBlock
Guard I/O connectivity have receiver DIP
switches 1, 2, and 3 disabled. The configurable
features allowed for this GuardShield light
curtain are fixed and floating blanking and
beam coding.