Original instructions, Examples of range of use, Guardshield laser alignment – Rockwell Automation 440L GuardShield Type 4 and Remote Teach User Manual User Manual
Page 8: Safety functions
 
GuardShield™ Safety Light Curtain User Manual
6
R
Original instructions
possible to use a standard GuardShield Type 4 POC pair as the last 
segment in a cascading system.
Examples of Range of Use
The GuardShield safety light curtain operates as a proper protective 
device only if the following conditions are met:
• The control of the machine must be electrical.
• The controlled machine must be able to be stopped any where
in the machines stroke or cycle.
• The transmitter and receiver must be mounted such that access
to the hazard is only through the light curtain’s protective field.
• The restart button must be located outside the hazardous area
such that it cannot be operated by a person working inside the 
hazardous area.
• The statutory and local rules and regulations must be observed
when installing and using the device.
Restart interlock is not available in GuardShield light curtains with 
ArmorBlock Guard I/O connectivity.
GuardShield Laser Alignment
The laser light source in the Integrated Laser Alignment system of the 
GuardShield light curtains is a Class 1, eye safe laser diode with a 
wavelength of 670 nm. 
This Class 1, eye safe laser is switched from a low output power state 
to a high output power state (and back again) by means of control 
circuitry which detects reflected laser light from a temporary blockage 
of the emitted laser light. This is most commonly accomplished by a 
person’s finger placed over the laser overlay window. There is also an 
automatic shutdown feature that switches the laser diode from the 
high power state to the low power state if there is no finger or other 
interruption detected for a period of five minutes.
During the high output mode of operation, the laser is pulsed at a rate 
of approximately 2 Hz in order to facilitate finger detection in high 
ambient light conditions.
Safety Functions
The GuardShield safety light curtain offers a variety of functions, 
which are integral to the system. 
Operating modes, functions and features of the GuardShield system 
are activated through DIP switch settings.
Guard Only
When in the guard only mode of operation, the light curtain operates 
as an on/off device, meaning the OSSD outputs switch off/on 
according to an obstruction or clearing of the detection field. The 
GuardShield is shipped from the factory configured in Guard only 
mode.
Start Interlock
The start interlock prevents the OSSD outputs from switching to ON 
state after power up of the system with the protective field 
unobstructed. A manual reset of the system is required for the 
GuardShield to enter the ON state. 
This can be accomplished by one of two methods.
• Actuation of a momentary N.O. push button
• Interruption and restoration of the protective field within one
second.
Activation of this mode of operation and selection of the resetting 
method is through DIP-switch settings. Indication of this mode of 
operation is through illumination of a yellow LED on the GuardShield 
receiver.
Start interlock is not available on middle and end segments of a 
cascading GuardShield system, however, it is possible to configure this 
operating mode in the host segment allowing the whole cascading 
system to operate in this mode. Start interlock is not available in 
GuardShield light curtains with ArmorBlock Guard I/O connectivity.
Restart Interlock
The restart interlock mode of operation prevents the OSSD outputs 
from switching to ON after interruption and clearance of the 
protective field. A manual reset of the GuardShield system is required. 
Resetting of the system is accomplished through a momentary N.O. 
push button or key switch. Configuration and activation of this mode 
of operation is through DIP-switch settings. The restart interlock 
mode is indicated by the illumination of a yellow LED on the 
GuardShield receiver.
Restart interlock is not available on middle and end segments of a 
cascading GuardShield system, however, it is possible to configure this 
operating mode in the host segment allowing the whole cascading 
system to operate in this mode.
Restart interlock is not available in GuardShield light curtains with 
ArmorBlock Guard I/O connectivity.
Relay Monitoring (MPCE/EDM)
The relay monitoring function is an input signal to the GuardShield 
receiver and is used to monitor the state of the protected machinery’s 
primary control contactors or other final switching device. Detection 
of unsafe conditions such as welded contacts, cause the GuardShield 
to enter a lockout condition (OSSDs OFF). Activation of this mode of 
operation is through DIP-switch setting in the GuardShield receiver.
IMPORTANT
Additional measures may be necessary to 
ensure that the ESPE does not fail to danger 
when other forms of light radiation are present 
in a particular application (i.e., use of cableless 
control devices on cranes, radiation from weld 
spatter or effects from strobe lights).
ATTENTION
Use of controls or adjustments or performance 
of procedures other than those specified herein, 
may result in hazardous radiation exposure.
IMPORTANT
The protective system must be tested for proper 
operation after each and every change to the 
configuration.