GuardShield™ Safety Light Curtain User Manual

20

R

Original instructions

System Status Indicators

8 through 13 = Fault conditions

Flash rate is approximately 2 Hz (2 times per second)

Note: For fault conditions 8 through 13, see Troubleshooting guide on page 19.

Receiver LEDs

Transmitter LEDs

Condition No.

OSSDs

OFF

Red

OSSDs

ON

Green

Blanking

Yellow

Alignment

Amber

Interlock

Yellow

Power

On

Amber

Emitting

Yellow

1

OFF

ON

OFF

OFF

OFF

ON

ON

2

ON

OFF

OFF

OFF

OFF

ON

ON

3

ON

OFF

OFF

ON

OFF

ON

ON

4

ON

OFF

OFF

OFF

ON

ON

ON

5

OFF

ON

ON

OFF

OFF

ON

ON

6

OFF

ON

FLASH

OFF

OFF

ON

ON

7

ON

OFF

OFF

OFF

OFF

ON

OFF

8

FLASH

OFF

OFF

OFF

OFF

ON

ON

9

ON

OFF

OFF

OFF

OFF

FLASH

ON

10

FLASH

OFF

OFF

ON

OFF

ON

ON

11

FLASH

OFF

OFF

OFF

ON

ON

ON

12

FLASH

OFF

DATA TRANS

OFF

OFF

ON

ON

13

ON

OFF

OFF

OFF

OFF

FLASH

DATA TRANS

Condition No.

Description

1

Guard only mode, light curtain unobstructed (aligned, not in interlock)

2

Guard only mode, light curtain interrupted (aligned, not in interlock)

3

Guard only mode, misaligned (not in interlock)

4

Guard only mode, in start or restart interlock (aligned)

5

Fixed blanking mode (aligned, not in interlock)

6

Floating or Floating/Fixed Blanking mode (aligned, not in interlock)

7

Transmitter test input active (pin 4)

8

Internal fault, receiver

9

Internal fault, transmitter

10

External fault (OSSD short to ground, +V, or cross connection)

11

External fault (MPCE/EDM error)

12

Configuration mode (receiver access door open)

13

Configuration mode (transmitter access door open)

Receiver

Transmitter

OSSDs OFF

Blanking

Emitting

OSSDs ON

Interlock

Alignment

POWER ON