Chapter 5 SCADA Applications
5. On the connection tab, enter the desired Requested Packet
Interval (RPI).
Do not enter an RPI less than 50 mS.
6. Click OK, then Save and download the offline project into the
controller.
The data from the user configured table is read into the controller tag
[Module Name]:I.Data without any further logic programming, at the
selected RPI rate.
A power monitor connected instance may be owned by only one
controller. An error results if you attempt to establish a connection
with more than one controller. You may use explicit messaging to
read the F9 table from any number of controllers.