85

Powermonitor 1000 Data Tables Appendix A

33

kVAR Demand

34

kVA Demand

35

PF Demand

Load Factor Log Results Parameters

CSP File No.

F30

CIP Instance

23

No. of Elements

14

No. of Words

28

Data Type

Float

Data Access

Read

Min/Max Parameter List

No.

Parameter

TR1

TR2

EM3

Load Factor Log Results

Element
No.

Modbus
Address

Element Name

Range

TR

1

TR

2

EM

1

EM

2

EM

3

Description

0

31101-2

Record Number

1…13

The record number of this data.

1

31103-4

End Date
yy/mm/dd

-

The date that this record was stored.

2

31105-6

Elapsed Time

0.000…
9,999,999

Amount of time (in hours) that has
elapsed since the last clear of the peak
and average values. Updated at the end
of each demand interval.

3

31107-8

Peak Demand
kWatts

+/-
0.000…9,999,
999

The largest magnitude demand for
kwatts that occurred over all of the
demand intervals since the last clear
command or auto-clear day.

4

31109-10

Average Demand
kWatts

+/-
0.000…9,999,
999

A running average of demand for
kwatts from the end of each demand
period since the last clear command or
auto-clear day.

5

31111-12

Load Factor
kWatts

0…100%

Average Demand kW / Peak Demand
kW. This is a demand management
metric that indicates how ‘spiky’ (or
‘level’) a load is over a period of time
(usually 1 month). A value approaching
100% indicates a constant load.

Advertising