Powermonitor 1000 Data Tables Appendix A

3

30107-8

Current Input
Missing

-1…123

Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing

4

30109-10

Current Input
Inverted

-1…123

Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted

5

30111-12

Voltage Rotation

-1…132

Reports on all three phases. The
reported sequence represents
each phase. Example: 123 =
Phase 1 then phase 2 then phase
3
-1 = Test not run
4 = Invalid rotation
1…132 designating phase and
rotation.

6

30113-14

Current Rotation

-1…321

Reports on all three phases. The
reported sequence represents
each phase. Example: 123 =
Phase 1 then phase 2 then phase
3
-1 = Test not run
4 = Invalid rotation
1…321 designating phase and
rotation.

7

30115-16

Voltage Phase 1
Angle

Degrees

0…359.99

Shows the present phase angle
of this channel. Should always be
0 degrees for voltage phase 1.

8

30117-18

Voltage Phase 1
Magnitude

Volts

0…9,999,999

Shows the present magnitude of
this phase.

9

30119-20

Voltage Phase 2
Angle

Degrees

0…359.99

Shows the present phase angle
of this channel.

10

30121-22

Voltage Phase 2
Magnitude

Volts

0…9,999,999

Shows the present magnitude of
this phase.

11

30123-24

Voltage Phase 3
Angle

Degrees

0…359.99

Shows the present phase angle
of this channel.

Wiring Diagnostics Results

Element
No.

Modbus
Address

Element Name

Units

Range

TR

1

TR

2

EM

1

EM

2

EM

3

Description