89

Powermonitor 1000 Data Tables Appendix A

Time of Use Log Results - Apparent Energy and Demand Parameters

CSP File No.

F33

CIP Instance

26

No. of Elements

12

No. of Words

24

Data Type

Float

Data Access

Read

Time of Use Log Results - Apparent Energy and Demand

Element
No.

Modbus
Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

31401-2

Record Number

1…13

The record number of the log. Record 0 is
always the current record before being
logged.

1

31403-4

Time Stamp Start
Date (yy/mm/dd)

-

The Date this record was started.

2

31405-6

Time Stamp End
Date (yy/mm/dd)

-

The Date this record was ended.

3

31407-8

Off Peak GVAh
Net

+/- 0…
9,999,999

Net Off peak giga VA hours

4

31409-10

Off Peak kVAh
Net

+/- 0.000…
999,999

Net Off Peak kilo VA hours

5

31411-12

Off Peak kVA
Demand

+/- 0.000…
9,999,999

Off Peak Demand for kilo VA

6

31413-14

Mid Peak GVAh
Net

+/- 0…
9,999,999

Net Mid Peak giga VA hours

7

31415-16

Mid Peak kVAh
Net

+/- 0.000…
999,999

Net Mid Peak kilo VA hours

8

31417-18

Mid Peak kVA
Demand

+/- 0.000…
9,999,999

Mid Peak Demand for kilo VA

9

31419-20

On Peak GVAh
Net

+/- 0.000…
9,999,999

Net On Peak giga VA hours

10

31421-22

On Peak kVAh
Net

+/- 0…
999,999

Net On Peak kilo VA hours

11

31423-24

On Peak kVA
Demand

+/- 0.000…
9,999,999

On Peak Demand for kilo VA

Advertising