Appendix A Powermonitor 1000 Data Tables
User Configurable Table Setup Parameters
CSP File No.
N36
CIP Instance
29
Applies to
EM3 only
No. of Elements
17
No. of Words
17
Data Type
Integer
Data Access
Read/Write
User Configured Table Setup
Element
No.
Modbus
Address
Element Name
Default Value
Range
Description
0
41001
Password
0
0…9999
Required for configuration,
returns -1.
1
41002
Selection for Parameter #1
29 (L1 Current)
0…110
2
41003
Selection for Parameter #2
30 (L2 Current)
3
41004
Selection for Parameter #3
31 (L3 Current)
4
41005
Selection for Parameter #4
37 (L1-L2 Voltage)
5
41006
Selection for Parameter #5
38 (L2-L3 Voltage)
6
41007
Selection for Parameter #6
39 (L3-L1 Voltage)
7
41008
Selection for Parameter #7
41 (Frequency)
8
41009
Selection for Parameter #8
52 (Total Real Power)
9
41010
Selection for Parameter #9
56 (Total Reactive Power)
10
41011
Selection for Parameter #10
60 (Total Apparent Power)
11
41012
Selection for Parameter #11
48 (3 Phase True Power Factor)
12
41013
Selection for Parameter #12
70 (Real Energy Net (kWh))
13
41014
Selection for Parameter #13
62 (Status 1 Count x1)
14
41015
Selection for Parameter #14
64 (Status 2 Count x1)
15
41016
Selection for Parameter #15
79 (Real Power Demand)
16
41017
Selection for Parameter #16
8 (Status Input States)