Appendix A Powermonitor 1000 Data Tables

8

40509

ON Peak PM
hours

7

0…409
5

This bit map selects any PM hours that
are designated as ON Peak. Example:
The hours from 12 PM to 3 PM is
designated as bit 0 through bit 2 = 7d

Bit0= 12 PM…1 PM
Bit1= 1 PM…2 PM
Bit2= 2 PM…3 PM

Bit11= 11PM…12 PM
Default is 12 PM…3 PM

9

40510

Load Factor log
Auto Log
Setting

31

0…31

Automatically stores the current peak,
average, and load factor results as a
record in the non-volatile load factor log
and resets the log at the specified day of
the month.

0 = Disables the auto clear feature.
1 = Store and clear the table on the 1st
day of each month.
2 = 2nd Day
3 = 3rd day

29…31 = Store and clear table at the
last day of the month.

10

40511

Reserved

0

0

Reserved for future use.

11

40512

Reserved

0

0

Reserved for future use.

Log Configuration

Element
No.

Modbus
Address

Element Name Default

Value

Range

TR1

TR2

EM1

EM2

EM3

Description

Command Table Parameters

CSP File No.

F16

CIP Instance

9

No. of Elements

22

No. of Words

44

Data Type

Float

Data Access

Write