13. Relay Contacts and Inhibit Input

The DC-UPS is equipped with relay contacts and signal inputs for remote monitoring and control of the input.

Relay contacts:
Ready:

Contact is closed when battery is charged more than 85%, no wiring failure is recognized, input
voltage is sufficient and inhibit signal is inactive.

Buffering: Contact is closed when unit is buffering.
Replace Battery:

Contact is closed when the unit is powered from the input and the battery quality test (SoH test)

reports a negative result.

Relay contact ratings

max

60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load

min

1mA at 5Vdc min.

Isolation voltage

max

500Vac, signal port to power port

Signal input:

7 +

5,1V

3mA

Inhibit

8 -

Inhibit:

The inhibit input disables buffering. In normal mode, a static signal is
required. In buffer mode, a pulse with a minimum length of 250ms is
required to stop buffering. The inhibit is stored and can be reset by
cycling the input voltage. See also section 26.1 for application hints.

Signal voltage

max. 35Vdc

Signal current

max. 6mA, current limited

Inhibit threshold

min.

6Vdc, buffering is disabled above this threshold level.

max. 10Vdc

Isolation

nom. 500Vac, signal port to power port

Restrictions apply when using the signal and relay contacts in a Haz-Loc environment:

The Buffering, Ready and Replace Battery contact is intended to be used for a separately investigated nonincendive field wiring

and/or field wiring apparatus. The DC-UPS may be located in a Class I, Division 2 (Group A, B, C or D) hazardous (classified)
location. Associated apparatus must be installed in accordance with its manufacturer’s control drawing and Article 504 of the
National Electrical Code (ANSI/NFPA 70) for installation in the United States, or Section 18 of the Canadian Electrical Code for

Installations in Canada.

Selected associated apparatus must be third part listed as providing nonincendive field circuits for the application, and have Voc
not exceeding Vmax, Isc not exceeding Imax.

Non associated nonincendive field wiring apparatuses shall not be connected in parallel unless this is permitted by the associated
nonincendive field wiring apparatuses approval.