All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

6

Rockwell Automation Publication 1606-RM036A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

7. Output in Buffer Mode

If the input voltage falls below a certain value (transfer threshold level), the DC-UPS starts buffering without any
interruption or voltage dips. Buffering is possible even if the battery is not fully charged.

nom.

DC 24V

Output voltage is stabilized and independent from
battery voltage

Output voltage in buffer mode

22.45V

±1%, at no load,

22.25V

±1%, at 10A output current

typ.

80mV higher than the output voltage in buffer mode

Transfer threshold for buffering

Ripple and noise voltage

max.

20mVpp

20Hz to 20MHz, 50Ohm

Output current

nom.

10A

Continuously allowed

15A

< 5s with full output voltage *)

Short-circuit current

min.

17.9A

Load impedance 100mOhm **)

max.

21A

Load impedance 100mOhm **)

*)

If the output current is in the range between 10A and 15A for longer than 5s, a hardware controlled reduction of the

maximal output current to 10A occurs. If the 10A are not sufficient to maintain the 24V, buffering stops after another 5s.
Buffering is possible again as soon as the input voltage recovers.

**)

If the nominal output voltage cannot be maintained in buffer mode, the DC-UPS switches off after 5s to save battery
capacity.

Fig. 7-1 Buffering transition, definitions

Fig. 7-2 Transfer behavior, typ.

Buffer mode

Output
voltage

24V

28V

Input
voltage

t

t

Transfer

threshold

5 00 m s /D IV

0 V

Output
Voltage

Input Voltage

2 4V

2 2. 25 V a t 1 0A

2 4V

Fig. 7-4 Output voltage vs. output current

in buffer mode, typ.

Fig. 7-3 Available output current in

buffer mode

Output Voltage

A

B
C

Continuously available
Available for 5s then auto switching to curve

Buffering will stop after 5s.

D

0

0

5

10

15

20

5

10

15

25V

20

25A

Output

Current

A

B

C

D

D

Buffering will stop after 5s.

Output

Current

0

0

5 Sec.

15A

10A

Time

5A

BonusPower