All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

16

Rockwell Automation Publication 1606-RM036A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

17. EMC

The unit is suitable for applications in industrial environments as well as in residential, commercial amnd light industry
environments without any restrictions. The CE Mark is in conformance with EMC guidelines 89/336/EEC and 93/68/EEC
and the low-voltage directive (LVD) 73/23/EEC, 93/68/EEC.
A detailed EMC report is available on request.

EMC Immunity

EN 61000-6-1, EN 61000-6-2

Generic standards

Electrostatic discharge

EN 61000-4-2

Contact discharge
Air discharge

8kV
15kV

Criterion A*)
Criterion A *)

Electromagnetic RF field

EN 61000-4-3

80MHz-1GHz 10V/m Criterion

A

Fast transients (Burst)

EN 61000-4-4

Out- and input lines

2kV

Criterion A

Signal lines **)

2kV

Criterion A

Surge voltage

EN 61000-4-5

Output + -
Input + -
+ / - housing

500V
500V
500V

Criterion A
Criterion A
Criterion A

Conducted disturbance

EN 61000-4-6 0,15-80MHz

10V

Criterion

A

*)

Grounded to the DIN rail

**) Tested

with

coupling

clamp

EMC Emission

EN 61000-6-3, EN 61000-6-4

Generic standards

Conducted emission

EN 55022

Input lines

Class B *)

EN 55022

Output lines

Class B *)

Radiated emission

EN 55011, EN 55022

Class B

This device complies with FCC Part 15 rules.

Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and 2) this
device must accept any interference received, including interference that may cause undesired operation.

*)

Informative measurement with voltage probe

Switching frequencies

The DC-UPS has three converters with three different
switching frequencies included.

Switching frequency of boost converter

100kHz

Constant frequency

Switching frequency of electronic output cu rrent limitation

78kHz

Constant frequency

Switching frequency of battery charger

19.5kHz

Constant frequency