All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

4

Rockwell Automation Publication 1606-RM036A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

5. Input

Input voltage

nom. DC

24V

Input voltage ranges

nom.

22.5 to 30Vdc

Continuous operation, see Fig. 5-1

30 to 35Vdc

Temporarily allowed, no damage to the DC-UPS *)

35Vdc

Absolute maximum input voltage with no damage to the
DC-UPS

0 to 22.5Vdc

The DC-UPS switches into buffer mode and delivers
output voltage from the battery if the input was above
the turn-on level before and all other buffer conditions
are fulfilled.

Allowed input voltage ripple

max. 1.5Vpp

Bandwidth

<400Hz

1Vpp

Bandwidth 400Hz to 1kHz

Allowed voltage between input
and earth (ground)

max. 60Vdc

or

42.4Vac

Turn-on voltage

typ.

22.8Vdc

The output does not switch on if the input voltage does
not exceed this level.

max. 23Vdc

Input current **)

typ. 120mA

Internal

current

consumption

typ.

1.1A

Current consumption for battery charging in constant
current mode at 24V input See Fig. 8-2 ***)

External capacitors on the input

No limitation

*) The DC-UPS shows “Check Wiring” with the red LED and buffering is not possible
**) The total input current is the sum of the output current plus the current required to charge the battery during the charging

process and the current which is needed to supply the DC-UPS itself. See also Fig. 5-2. This calculation does not apply
in overload situations where the DC-UPS limits the output current, therefore see Fig. 5-3

.

***) Please note: This is the input current and not the current flowing into the battery in the process of charging. The battery current

is indicated in section 8.

Fig. 5-1 Input voltage range

Fig. 5-2 Input current, definitions

A: Rated input voltage range
B: Temp. allowed, no harm to the unit
C: Absolute max. input voltage
D: Buffer mode

V

IN

18

30

35V

22.5

0

A

B

C

D

V

OUT

Internal

current

consumption

Current

consumption

for battery

charging

Output
Current

Input

Current

Fig. 5-3 Input current and output voltage vs.

output current, typ. (battery fully charged)

Electronic output current limitation
The DC-UPS is equipped with an electronic output
current limitation. This current limitation works
in a switching mode which reduces the power
losses and heat generation to a minimum. As a
result, the output voltage drops since there is not
enough current to support the load. A positive
effect of the current limit ation in switching mode
is that the input current goes down despite an
increase in the output current resulting in less
stress for the supplying source.