Battery input – Rockwell Automation 1606-XLS240-UPS Power Supply Reference Manual User Manual

Page 7

Advertising
background image

All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

Rockwell Automation Publication 1606-RM036A-EN-P — April 2014

7

Bulletin 1606 Switched Mode Power Supplies

8. Battery Input

The DC-UPS requires one 12V VRLA battery to buffer the 24V output.

Battery voltage

nom.

DC 12V

Use one maintenance-free 12V VRLA lead acid battery or
one battery module which is listed in the Accessories
section.

9.0 – 15.0V

Continuously allowed, except deep discharge protection

Battery voltage range

max.

35Vdc

Absolute maximum voltage with no damage to the unit

typ.

7.4V

Above this voltage level battery charging is possible.

Allowed battery sizes

min.

3.9Ah

max. 40Ah

max.

100mOhm

See individual battery datasheets for this value.

Internal battery resistance

Battery charging method

CC-CV

Constant current, constant voltage mode

Battery charging current (CC-mode)

nom.

1.5A

Independent from battery size,

max.

1.7A

Corresponding 24V input current see Fig. 8-2

End-of-charge-voltage (CV-mode)

13.4-13.9V

Adjustable, see section 14.

Battery charging time

typ.

5h *)

For a 7Ah battery

typ.

17h *)

For a 26Ah battery

Battery discharging current **)

typ.

21A

Buffer mode, 10A output current, 11.5V on the battery
terminal of the DC-UPS, see

Fig. 8-1 for other parameters

typ.

0.3A

Buffer mode, 0A output current

max.

50

μ

A

At no input, buffering had switched off, all LEDs are off

typ.

270mA

At no input, buffering had switched off, yellow LED
shows “buffer time expired” (max. 15 minutes)

typ.

10.5V

At 0A output current

Deep discharge protection ***)

typ.

9.0V

At 10A output current

*) The charging time depends on the duration and load current of the last buffer event. The numbers in the table represent a

fully discharged battery. A typical figure for a buffer current of 10A is 3h 20 min (200 min) for a 7Ah battery.

**) The current between the battery and the DC-UPS is more than twice the output current. This is caused by boosting the 12V

battery voltage to a 24V level.

This high current requires large wire gauges and short cable length for the longest possible

buffer time. The higher the resistance of the connection between the battery and the DC-UPS, the lower the voltage on the
battery terminals which increases the discharging current. See also section 25 for further installation instructions.

***) To ensure longest battery lifetime, the DC-UPS has a battery deep discharge protection feature included. The DC-UPS stops

buffering when the voltage on the battery terminals of the DC-UPS falls below a certain value. The yellow LED will show
“buffer time expired” for a period of 15 minutes after the unit stopped buffering.

Fig. 8-1 Battery discharging current

vs. output current, typ.

Fig. 8-2 Required input current vs. input

voltage for battery charging

Battery Current

0

0

10

20

5

15

25

30A

2.5

7.5

10

15A

12.5

5

Output

Current

Voltage on
battery terminal
of the DC-UPS:
A: 10.5V
B: 11V
C: 12V

A

B

C

Input Current

0

23

0.5

1.0

0.25

0.75

1.25

1.5A

Input

Voltage

24

25

26

28V

max. (battery charging c

urrent 1.7A)

27

typ. (battery charging c

urrent 1.5A)

Advertising