Rockwell Automation 1606-XLS240-UPS Power Supply Reference Manual User Manual
Page 13

All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM036A-EN-P — April 2014
13
Bulletin 1606 Switched Mode Power Supplies
Fig. 13-1 Contact control drawing for use in Haz-Loc
environments
+ -
Ready
DC-
UPS
1
Hazardous
Location
Non Hazardous
Location
Apparatus
Voc
Isc
Input
Output
+ -
+
-
Battery
Buffering
Voc
Isc
Replace
Battery
Voc
Isc
2
3
4
5
6
Selected barriers must have entity parameters such that
Voc < V max, lsc < lmax,
Ca > Ci + Ccable, La > Li + Lcable.
For Ccable and Lcable, if the capacitance per foot
or the inductance per foot is not known, then the
following values shall be used: Ccable = 60pF/foot
and Lcable = 0.2µH/foot.
Contact current: I max = 50mA
Contact voltage: V max. = 35V (DC or AC)
Max. associated circuit capacitance Ci = 0
Max. associated circuit inductance Li = 0
No polarity requirement