All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

Rockwell Automation Publication 1606-RM036A-EN-P — April 2014

13

Bulletin 1606 Switched Mode Power Supplies

Fig. 13-1 Contact control drawing for use in Haz-Loc

environments

+ -

Ready

DC-

UPS

1

Hazardous
Location

Non Hazardous
Location

Apparatus

Voc

Isc

Input

Output

+ -

+

-

Battery

Buffering

Voc

Isc

Replace
Battery

Voc

Isc

2

3

4

5

6

Selected barriers must have entity parameters such that

Voc < V max, lsc < lmax,

Ca > Ci + Ccable, La > Li + Lcable.

For Ccable and Lcable, if the capacitance per foot
or the inductance per foot is not known, then the
following values shall be used: Ccable = 60pF/foot
and Lcable = 0.2µH/foot.

Contact current: I max = 50mA

Contact voltage: V max. = 35V (DC or AC)
Max. associated circuit capacitance Ci = 0
Max. associated circuit inductance Li = 0
No polarity requirement