PowerMonitor W250 Unit Overview

PowerMonitor W250 Data Overview

The PowerMonitor W250 unit sends data to the wireless receiver periodically.
The meter data is split into three sections:

Cumulative Energy Consumption Metering Data: The power monitor

transmits accumulated real, reactive, and apparent energy, per-phase and
total, once per minute. The transmission is accompanied with the time
stamp of the most recent reading.

Interval Metering Data: The power monitor sends, at the end of the user-

selected interval, a time-stamped record of the following data: real,
reactive, and apparent energy per phase and sum; minimum voltage per
phase and maximum current per phase during recording interval;
frequency.

Node Identification, Configuration, and Status: Node configuration and

version; recording interval time setup, command and status word.

PowerMonitor W250 Model Description

The following table lists the available models of the PowerMonitor W250 unit.

Table 2 - Model Description

Cat. No.

Description

Current
Rating (A)

Max
Voltage

(1)

Delta/Wye

Current
Sensing

Model
Code

1425-D1002-MOD

PowerMonitor Wireless, 100A, 300V Delta

100

300

Delta, 3 W

CT

111

1425-D1002-MOD-480

PowerMonitor Wireless, 100A, 480V Delta

100

480

Delta, 3 W

Rogowski Coil

111

1425-W1003-MOD

PowerMonitor Wireless, 100A, 300V Wye

100

300

Wye, 4 W

CT

000

1425-D2002-MOD

PowerMonitor Wireless, 200A, 300V Delta

200

300

Delta, 3 W

CT

111

1425-W2003-MOD

PowerMonitor Wireless, 200A, 300V Wye

200

300

Wye, 4 W

CT

000

1425-D5002-MOD

PowerMonitor Wireless, 500A, 300V Delta

500

300

Delta, 3 W

CT

111

1425-D5002-MOD-480

PowerMonitor Wireless, 500A, 480V Delta

500

480

Delta, 3 W

Rogowski Coil

111

1425-W5003-MOD

PowerMonitor Wireless, 500A, 300V Wye

500

300

Wye, 4 W

CT

000

1425-D10002-MOD

PowerMonitor Wireless, 1000A, 300V Delta

1000

300

Delta, 3 W

CT

111

1425-W10003-MOD

PowerMonitor Wireless, 1000A, 300V Wye

1000

300

Wye, 4 W

CT

000

1425-D20002-MOD

PowerMonitor Wireless, 2000A, 300V Delta

2000

300

Delta, 3 W

CT

111

1425-D20002-MOD-480

PowerMonitor Wireless, 2000A, 480V Delta

2000

480

Delta, 3 W

Rogowski Coil

111

1425-W20003-MOD

PowerMonitor Wireless, 2000A, 300V Wye

2000

300

Wye, 4 W

CT

000

(1) Maximum voltage on sensing terminals must not exceed the following:

a.300V Delta, 3 W: 300V AC line-to-line maximum
b.300V Wye, 4 W: 300V AC line-to-neutral maximum
c.480V Delta, 3 W: 520V AC line-to-line, 300V AC line-to-neutral maximum