Hardware Installation
Chapter 2
The PC Receiver's Device ID high byte determines the maximum number of
devices supported in the network.
The Group ID and Device ID should not be modified except under exceptional
circumstances. One such circumstance would be operating two or more
independent PowerMonitor W250 networks in such close proximity that RF
interference with each other occurs. Please contact Rockwell Automation
support services for more information or if assistance is required.
PC Receiver Connection
This section describes the RS-232 and RS-485 connections.
RS-232 Data Port Use and Configuration
DB-9 style connector: RS-232 Data Port connector with standard DCE
connections for transmit data, receive data, RTS input, and CTS output.
The PC Receiver is factory configured with the following parameters:
• Communication Rate - 115,200
• Data Bits - 8
• Parity - None
• Stop Bits - 1
IMPORTANT
The device ID low byte defines the Modbus network address for the module.
The Modbus address of each device on the network must be unique.
Table 13 - Number of Devices
PC Receiver ID High Byte
Max Number of Devices
170 10
200 100
220 200