Rockwell Automation 1425 PowerMonitor Wireless 250 User Manual
Page 43

Rockwell Automation Publication 1425-UM001A-EN-P - January 2012
43
Software Interface
Chapter 3
RF Communication Configuration and Status Modbus Register Table
This table lists the common registers used by all devices (power monitors,
routers, and PC receiver).
Table 22 - RF Communication Configuration and Status
Modbus Register
Description
Type/Length
Storage
Unit
Access
201 Hop
count
U16
V
R
202
First hop ID
U16
V
R
203
Last hop ID
U16
V
R
204
RSSI (high byte) and Supply
voltage (low byte)
U16 V
R
220
Device ID (high byte and
low byte)
U16 NV
R
221
Group ID (high byte and
low byte)
U16 NV
R
222 Sampling
interval
U16 NV
R
224 Network
channel
(11…26)
U16 NV
R
347
Device ID (high byte and
low byte)
U16
NV
See warning below
348
Group ID (high byte and
low byte)
U16
NV
See warning below
349 Sampling
interval
U16 V
W
351
Network channel (11…26) U16
NV
W
WARNING: Do not change the value of the Device ID or Group ID, registers 347
and 348. Doing so will cause the device to drop off the network and require
factory service to restore operation.
Table 23 - Information for
Term
Description
Comments
NV
Nonvolatile
Value is restored after a power cycle
V
Volatile
Value is not restored after a power
cycle
U16
Unsigned 16-bit INT
Range 0…65,535
High byte
Bits 8…15
Low byte
Bits 0…7