lists apparent energy raw values (one phase/sum of phases) at varying
percent of nominal phase currents with nominal voltage 240V or 480V for SP2
model.
Maximum Current (register 43…45)
The rms current is averaged over 10 cycles (200 mS in a 50 Hz system, 167 ms in
a 60 Hz system). The maximum average current in each phase, measured during
the recording interval, is kept in registers 43…45.
Minimum Voltage (register 46…48)
The rms voltage for each phase is averaged over 10 cycles. The minimum voltage
value measured during the recording interval is kept in registers 46…48.
Model Configuration (register 49)
Table 21 - Apparent Energy Raw Values
Load Current
25% Ipn
50% Ipn
100% Ipn
120% Ipn
Interval Time (min)
5
1600 / 4800
3200 / 9600
6400 / 19,200
7680 /23,040
6
1920 / 5760
3840 / 11,520
7680 / 23,040
9216 /27,648
10
3200 / 9600
6400 / 19,200
12,800 / 38,400
15,360 / 46,080
12
3840 / 11,520
7680 / 23,040
15,360 / 46,080
18,432 / 55,296
15
4800 / 14,400
9600 / 28,800
19,200 / 57,600
23,040 / 69,120
20
6400 / 19,200
12,800 / 38,400
25,600 / 76,800
30,720 / 92,160
30
9600 / 28,800
19,200 / 57,600
38,400 / 115,200 46,080
/
138,240
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0
0
1 1
1
Connection
Diagram
Voltage
Range
Not Used
Reserved
100 A
200 A
500 A
1000 A
2000 A
Rated Current
300V Maximum
520V Maximum
Bit Number
3-wire Delta
4-wire Wye
0 1
0 0
0 1
0 1
0 1
1 0
1 0
0 0
1 0
1 0
0
0
0
1