Hardware Installation

Chapter 2

Rogowski Coil

1. Observe the correct phase assignment of Rogowski coils with respect to

the voltage phase connections.

Refer to the wiring diagram for the applicable PowerMonitor W250
model. If phase assignment and polarity are not correctly observed, the
PowerMonitor W250 unit will produce incorrect energy data.

2. Verify that the arrow (3) points in the direction of current flow from the

supply (line) to the load.

3. Close the Rogowski (2) coil around the cable (1).

Be sure that the coil is well locked (fully inserted until a click is heard).

Figure 22 - Rogowski Coil Mounting

The Rogowski coil can be oriented freely around the cable/conductor. It
does not need to be attached. The position of the conductor within the
Rogowski coil does not affect the accuracy more than 0.5%.

ATTENTION: When installing a Rogowski coil, take care not to kink, pinch,
twist, or sharply bend the coil. Applying such mechanical stress to the coil may
reduce the accuracy of the PowerMonitor W250.

Load Side

Generator

Side

Load Side

Generator

Side

2

1

4

3

3

IMPORTANT

The arrow indicating the current direction must be inside the loop (3) when
closed as shown.