Rockwell Automation 1425 PowerMonitor Wireless 250 User Manual

Page 56

Advertising
background image

56

Rockwell Automation Publication 1425-UM001A-EN-P - January 2012

Appendix A

Specifications

Table 32 - Accuracy and Range

Parameter

Accuracy in % of Reading at 25 °C
(77 °F) (50/60 Hz)

Nom/Range

Voltage

Min value in interval 1.5%

D3 model: 240V 3-wire Delta/
90…300V AC line-to-line
277V line-to-neutral 4-wire WYE/
90…300V AC line-to-neutral
480 models: 480V 3-wire Delta/
90…520V AC line-to-line

Current

Max value in interval 1.5%

Depending on model, monitor load
range 100…2000 A

Frequency

Based of Phase 1

50 or 60 Hz/ 45…66 Hz

Energy functions: kWH

IEC 62053-21 Class 1 ± 1%

Energy functions: kVARH

IEC 62053-23 Class 3 ± 3%

Metering update rate

kWh, kVarh, kVAh counters @
1 minute;
Interval Energy Data @ configurable
5, 6, 10, 12, 15, 20, or 30 minutes

Table 33 - Input and Output Ratings

Attribute

Value

Control power

100…277V rms AC at 50/60 Hz (line-to-neutral)
2 W max consumption
24V DC power for 480 models

Table 34 - General Specifications

Attribute

Value

Dielectric withstand

CT-based model

3500V

Rogowski-based model

3500V

Terminal blocks

2.5 mm sq. for input voltage (18…24 AWG)
0.5 N•m (0.37 lb•ft)

Certifications

CE, cULus (power monitors only), FCC Part 15, Industry
Canada RSS-210