Status indicator description – Rockwell Automation 1425 PowerMonitor Wireless 250 User Manual

Page 31

Advertising
background image

Rockwell Automation Publication 1425-UM001A-EN-P - January 2012

31

Hardware Installation

Chapter 2

Status Indicator Description

The PowerMonitor W250 status indicator indicates the unit status as follows.

Figure 23 - PowerMonitor W250 Status Indicator

Table 10 - Status Indicator Description

Indicator Status

Description

1 blink, wait 2 seconds

Normal operation and direct serial communication mode from firmware revision 2.02.

2 blinks, wait 1 second

Radio module communication error: PowerMonitor W250 unit is unable to send data.

3 blinks, wait 1 second

Frequency out of range of 45…66 Hz.

4 blinks, wait 1 second

Communication and frequency error together.

5 blinks, wait 1 second

Device Error: Indicates a firmware checksum error. To recover, try a reset-meter
command followed by an OFF/ON sequence. If this does not reset this error, the
calibration memory is corrupt and the device needs to be returned to Rockwell
Automation for repair.

6 blinks, wait 1 second

Direct serial communication mode (factory use only) until firmware revision 2.01.

7 blinks, wait 1 second

Internal hardware failure. Please contact Rockwell Automation for service.

Status Indicator

Advertising