Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual
Page 136

Publication 1403-IN054B-EN-P - August 2001
D-2 Technical Specification
Refer to the DeviceNet Cable System Planning and Installation manual
(Publication 1485-6/7/1) for network layout and design information.
Table D.2 DeviceNet Cables
Cable
Catalog Number
DeviceNet Cable, 50 meters (164 feet)
1485C-P1A50
DeviceNet Cable, 100 meters (328 feet)
1485C-P1A150
DeviceNet Cable, 150 meters (492 feet)
1485C-P1A300
Table D.3 Environmental Specifications
Operating Temperature
-40°C to +55°C (-40°F to +131°F)
-40°C to +60°C (-40°F to +140°F)
(1)
(1) For DeviceNet V2 only.
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Humidity
5 to 95 percent, non-condensing
Vibration
Operational: 0.006 in. DA/1.0G Sine,
10 to 500 Hz, 3 orthogonal axes
Non-Operational: 0.015 in DA/2.5G Sine,
10 to 500 Hz, 3 orthogonal axes.
Shock
Operaitonal: 15G, Half Sine, 11 ms duration,
3 orthogonal axes, 3 (+) and 3 (-)
pulses/axes, 18 pulses total.
Non-Operational: 30G, Half Sine, 11 ms
duration, 3 orthogonal axes, 3 (+) and 3 (-)
pulses/axes, 18 pulses total.
Current Load on DeviceNet Power Supply
100 mA MAX