Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual
Page 62

Publication 1403-IN054B-EN-P - August 2001
B-32 DeviceNet Data Tables
Instance 26 Attributes (L4, Unbalance & Frequency Snapshot
data)
Assembly Structure
Common Services
Attribute ID Access
Rule
Name
DeviceNet Data Type
3
Get
Data
Structure of
52 bytes (26 Words)
Param #
Parameter name
Data type
#bytes
Master Module Range
Word No.
1
L4 current
Float
4
0.0 to 9999x10
21
amps
1
2
2
Positive sequence current
Float
4
0.0 to 9999x10
21
amps
3
4
3
Negative sequence current
Float
4
0.0 to 9999x10
21
amps
5
6
4
% current unbalance
Float
4
0.0 to 100.0
7
8
5
AUX voltage
Float
4
0.0 to 9999x10
21
volts
9
10
6
Positive sequence voltage
Float
4
0.0 to 9999x10
21
volts
11
12
7
Negative sequence voltage
Float
4
0.0 to 9999x10
21
volts
13
14
8
% voltage unbalance
Float
4
0.0 to 100.0
15
16
9
Unused
Float
4
Returns 0.0
17
18
10
Last cycle frequency
Float
4
20.0 to 132.0
19
20
11
Phase rotation
Int
2
0 = No Rotation
1 = ABC
2 = ACB
21
12
Timestamp; date/time
Int x 4
8
Year
22
Month, Day
23
Hour, Minutes
24
Seconds, Hundredths
25
13
Snapshot log # being
returned
Int
2
1 to 50
26
Service
Code
Service Name
0Ehex
Get_Attributes_Single