Common services, Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual
Page 68

Publication 1403-IN054B-EN-P - August 2001
B-38 DeviceNet Data Tables
Common Services
Instance 32 Attributes (Event log configuration/readback log
select)
Assembly Structure
Common Services
5
Timestamp of last Min/Max reset
Int x 4
8
Year
13
Month, Day
14
Hour, Minutes
15
Seconds, Hundredths
16
6
Parameter # being returned
Int x 4
8
1 to 84
17
Param #
Parameter name
Data type
#bytes
Master Module Range
Word No.
Service
Code
Service Name
0Ehex
Get_Attributes_Single
Attribute ID Access
Rule
Name
DeviceNet Data Type
3
Get
Data
Structure of
6 bytes (3 Words)
Param #
Parameter name
Data type
#bytes
Master Module Range
Default
Setting
Word
No.
1
Password
Int
2
-1, 0-9999
Correct password is required to
configure/reconfigure Event log functionality,
but not required to select an Event log
record to be read back in the Event log read
assembly. If the user is only selecting an
Event log record to be read, set password to
–1.
0
1
2
Event log record to
be read
Int
2
1 to 100, Specifies a specific Event log
record to be read. 1 = most recent record.
2
3
Enable/disable save
of status input
changes to event
log
Int
2
0 = disable
1 = enable
0
3
Service
Code
Service Name
0Ehex
Get_Attributes_Single